An electrical box fill calculator determines whether a junction box has enough internal volume for the conductors, devices, clamps, and grounds you plan to install — as required by NEC Article 314.16. Overcrowding a box traps heat, damages wire insulation, and creates fire hazards. This calculator does the math so your installation is code-compliant and inspection-ready.

Wire Gauge

Select the largest wire size in the box. This determines device, ground, and clamp allowances.

Conductors

Count each insulated wire (hot, neutral) entering or originating in the box. Do not count ground wires here.

Devices, Grounds & Clamps

Each device yoke = 2× largest conductor volume (NEC 314.16(B)(4)).

All grounds count as 1× largest conductor volume total (NEC 314.16(B)(5)).

All internal clamps count as 1× largest conductor volume (NEC 314.16(B)(2)).

Each bonding jumper = 1× largest conductor volume (NEC 314.16(B)(5)).

Box to Check