A conduit fill calculator determines what percentage of a conduit's interior area is occupied by wires, and whether that percentage complies with NEC (National Electrical Code) Article 358-362 limits. The NEC caps fill at 53% for a single wire, 31% for two wires, and 40% for three or more wires to prevent heat buildup and allow future wire pulls. Choosing the correct conduit size upfront avoids costly rework.

Conduit Fill Calculator

Conduit Type & Size

Circuit Wires

Equipment Ground Wire (optional)

Fill %
NEC Max %
Total Wires
NEC Status

Fill Breakdown

Conduit type & size
Conduit interior area
Circuit wires (area per wire)
Circuit wires total area
Ground wire(s) total area
Total wire area
Fill percentage
NEC maximum (Article 358-362)
Remaining capacity

Minimum Conduit Size for Your Wires

Run the calculator to see recommended conduit sizes.

Visual Fill Gauge

0% 100%
Fill Warning (near limit) Over NEC limit

NEC Fill Limits — Quick Reference

Conductors Max Fill Reason
1 wire 53% Single conductor allows easier pull
2 wires 31% Two wires nest — stricter limit prevents binding
3+ wires 40% Standard fill — allows heat dissipation & future pulls

Conduit Interior Areas (sq in) — NEC Annex C

Trade Size EMT IMC PVC Sch 40
1/2" 0.304 0.342 0.285
3/4" 0.533 0.586 0.508
1" 0.864 0.916 0.832
1-1/4" 1.496 1.528 1.453
1-1/2" 2.036 2.071 1.986
2" 3.356 3.408 3.291